Orders accepted now — shipping resumes September 5, 2026 (575) 228-1390contact@xfmrdirect.com (575) 228-1390contact@xfmrdirect.com Request a Quote

200V to 208V Buck-Boost Transformers

200 to 208 volts is the smallest correction in this family and the one that gets argued about, because 200 volts is a legal reading. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.

2

Load current (amps)

Single-Phase

4.81 amps1 kVA · $253.51 · Ships in 2-3 weeks5 amps1.04 kVA · $254.45 · Ships in 2-3 weeks8.33 amps1.73 kVA · $265.22 · Ships in 2-3 weeks9.62 amps2 kVA · $265.22 · Ships in 2-3 weeks10 amps2.08 kVA · $265.22 · Ships in 2-3 weeks12.02 amps2.5 kVA · $265.92 · Ships in 2-3 weeks12.5 amps2.6 kVA · $266.54 · Ships in 2-3 weeks14.42 amps3 kVA · $275.54 · Ships in 2-3 weeks15 amps3.12 kVA · $277.95 · Ships in 2-3 weeks16.7 amps3.47 kVA · $282.31 · Ships in 2-3 weeks20 amps4.16 kVA · $288.88 · ✔ In Stock: 1020.83 amps4.33 kVA · $290.45 · ✔ In Stock: 1024.04 amps5 kVA · $410.89 · ✔ In Stock: 1025 amps5.2 kVA · $414.12 · Ships in 2-3 weeks26.6 amps5.53 kVA · $418.72 · Ships in 2-3 weeks28.85 amps6 kVA · $292.12 · ✔ In Stock: 1029.2 amps6.07 kVA · $423.35 · Ships in 2-3 weeks30 amps6.24 kVA · $423.43 · Ships in 2-3 weeks36.06 amps7.5 kVA · $423.43 · Ships in 2-3 weeks40 amps8.32 kVA · $424.27 · Ships in 2-3 weeks41.67 amps8.67 kVA · $425.55 · Ships in 5-6 weeks43.27 amps9 kVA · $519.99 · Ships in 2-3 weeks50 amps10.4 kVA · $533.90 · ✔ In Stock: 257.69 amps12 kVA · $545.56 · ✔ In Stock: 260 amps12.48 kVA · $547.85 · ✔ In Stock: 262.5 amps13 kVA · $549.22 · ✔ In Stock: 270 amps14.56 kVA · $708.95 · ✔ In Stock: 672.12 amps15 kVA · $714.09 · ✔ In Stock: 278.1 amps16.24 kVA · $1,260.27 · Ships in 2-3 weeks80 amps16.64 kVA · $728.61 · ✔ In Stock: 683.3 amps17.33 kVA · $731.38 · ✔ In Stock: 690 amps18.72 kVA · $843.27 · ✔ In Stock: 896.15 amps20 kVA · $853.53 · ✔ In Stock: 6120.19 amps25 kVA · $881.98 · ✔ In Stock: 8125 amps26 kVA · $884.06 · ✔ In Stock: 8144.23 amps30 kVA · $1,165.44 · ✔ In Stock: 8167 amps34.74 kVA · $1,194.04 · ✔ In Stock: 6180.29 amps37.5 kVA · $709.78 · ✔ In Stock: 8200 amps41.6 kVA · $1,698.16 · Ships in 2-3 weeks208 amps43.26 kVA · $1,706.99 · Ships in 2-3 weeks240.38 amps50 kVA · $913.40 · ✔ In Stock: 6250 amps52 kVA · $1,715.52 · ✔ In Stock: 4360.58 amps75 kVA · $1,204.77 · ✔ In Stock: 4

Three-Phase Delta

2.78 amps1 kVA · $430.08 · Ships in 2-3 weeks5 amps1.8 kVA · $432.30 · Ships in 2-3 weeks5.55 amps2 kVA · $432.30 · Ships in 2-3 weeks6.94 amps2.5 kVA · $432.30 · Ships in 2-3 weeks8.33 amps3 kVA · $434.46 · Ships in 2-3 weeks10 amps3.6 kVA · $567.20 · Ships in 2-3 weeks12.5 amps4.51 kVA · $583.45 · Ships in 2-3 weeks13.88 amps5 kVA · $583.45 · Ships in 2-3 weeks15 amps5.4 kVA · $583.45 · Ships in 2-3 weeks16.65 amps6 kVA · $586.32 · Ships in 2-3 weeks16.7 amps6.01 kVA · $586.36 · Ships in 2-3 weeks20 amps7.21 kVA · $586.36 · ✔ In Stock: 520.82 amps7.5 kVA · $589.29 · ✔ In Stock: 520.83 amps7.5 kVA · $589.29 · ✔ In Stock: 524.98 amps9 kVA · $760.28 · ✔ In Stock: 525 amps9.01 kVA · $760.40 · Ships in 2-3 weeks29.2 amps10.5 kVA · $776.97 · Ships in 2-3 weeks30 amps10.81 kVA · $776.97 · Ships in 2-3 weeks33.31 amps12 kVA · $778.08 · Ships in 2-3 weeks40 amps14.41 kVA · $802.21 · Ships in 2-3 weeks41.64 amps15 kVA · $1,050.48 · ✔ In Stock: 541.67 amps15.01 kVA · $804.63 · Ships in 5-6 weeks50 amps18.01 kVA · $804.63 · ✔ In Stock: 155.51 amps20 kVA · $804.63 · ✔ In Stock: 160 amps21.62 kVA · $806.63 · ✔ In Stock: 162.5 amps22.5 kVA · $808.66 · ✔ In Stock: 169.39 amps25 kVA · $1,221.04 · ✔ In Stock: 170 amps25.22 kVA · $1,223.73 · ✔ In Stock: 380 amps28.82 kVA · $1,257.67 · ✔ In Stock: 383.27 amps30 kVA · $1,262.50 · ✔ In Stock: 383.33 amps30.02 kVA · $1,262.51 · ✔ In Stock: 390 amps32.42 kVA · $1,632.96 · ✔ In Stock: 497.4 amps35.09 kVA · $1,750.79 · ✔ In Stock: 4104.09 amps37.5 kVA · $1,675.52 · ✔ In Stock: 4125 amps45 kVA · $1,712.03 · ✔ In Stock: 4138.79 amps50 kVA · $1,768.60 · ✔ In Stock: 4167 amps60 kVA · $1,828.64 · ✔ In Stock: 3200 amps72.05 kVA · $2,270.39 · Ships in 2-3 weeks208 amps74.94 kVA · $2,282.33 · Ships in 2-3 weeks208.18 amps75 kVA · $3,992.45 · ✔ In Stock: 4229.2 amps82.57 kVA · $4,005.78 · ✔ In Stock: 2250 amps90 kVA · $2,418.34 · ✔ In Stock: 2277.57 amps100 kVA · $1,821.03 · ✔ In Stock: 3312.27 amps112.5 kVA · $1,817.05 · ✔ In Stock: 3416.36 amps150 kVA · $2,120.82 · Ships in 2-3 weeks
Only exact rated-amperage matches that can be purchased online are shown. Without JavaScript, an amperage choice opens its exact product page.
✔ Recommended for your application

Sizing uses the correction winding only. Verify load current against the equipment nameplate and install per the included wiring diagram and applicable NEC requirements.

Quick answer

Measured input
200V
Required output
208V
Correction
Boost (raise voltage) · 4.0%
Size from
System phase and equipment nameplate amps
Technical details

200V to 208V technical overview

200 to 208 volts is the smallest correction in this family and the one that gets argued about, because 200 volts is a legal reading. ANSI C84.1 puts the Range A service minimum for a 208 volt system at 197 volts, so a panel measuring 200 is inside the standard and the utility is under no obligation to change it. A 200V to 208V buck-boost transformer applies roughly a 4 percent boost. Whether that is worth correcting turns on how much tolerance the connected equipment has left, not on whether the supply is compliant. Single-phase and three-phase, 10 through 60 amps.

Where 200V to 208V correction is used

This pair is chosen by the equipment rather than by the building, so the useful way to sort the applications is by how much input tolerance a load actually has.

Plenty of loads absorb 200 volts without help, which is why the correction is often skipped. A general-purpose induction motor nameplated 208-230V is rated against 208, and 200 volts is 3.8 percent low, comfortably inside the plus or minus 10 percent NEMA MG-1 describes.

The loads that drive the correction have a narrower window:

  • Packaged equipment offered only in a 208 volt rating, where 208 is the design point rather than the low end of a dual rating
  • Variable frequency drives, servo amplifiers and soft starters with undervoltage thresholds referenced to a 208 volt input
  • Elevator, hoist and material handling controllers that fault rather than derate
  • Laboratory, imaging and process instruments whose published input window is tighter than plus or minus 10 percent
  • Resistive heat, where nothing trips and the only symptom is output arriving about 7 percent short
  • 208 volt contactor and relay coils, which sit near dropout and open on a dip the motor would have ridden through

The supply is one of two situations: a building still distributing a legacy 200 volt nominal system, or a nominally 208 volt service that sits at the bottom of its band all day. Both produce the same reading and the same decision.

Why this 200V to 208V voltage pair matters

The case for correcting a compliant supply is about where the shortfall leaves you, not about whether it is permitted.

ANSI C84.1 separates service voltage from utilization voltage. On a 208 volt system the Range A service minimum is 197 volts and the Range A utilization minimum is 191. The gap between those two figures is the allowance the standard sets aside for the building's own wiring, and it is not generous. A service already reading 200 has about 9 volts of usable margin before voltage at a load reaches 191, and every foot of feeder and branch circuit spends part of it.

What that margin buys depends on the equipment. A motor built to plus or minus 10 percent has room to spare, which is why the motor is rarely the reason this pair gets specified. A controller with a stated window of plus or minus 5 percent has none: 200 volts is already 3.8 percent down, and the dip when a compressor starts on the same panel takes what is left. It does not degrade gradually. It trips, logs an undervoltage fault, and stays down until somebody resets it.

Installation notes

Sizing guidance

Work through it in three steps rather than starting from an amp rating.

First, identify the load that actually cares. Find the published input voltage window in the equipment documentation, not just the number on the nameplate, and confirm 200 volts falls outside it. If everything on the panel is a plus or minus 10 percent load, there is no correction to make.

Second, establish whether the 200 volt reading is fixed or load-dependent, because a buck-boost transformer applies a fixed ratio and follows its input. A legacy 200 volt system reads 200 at every hour, and a 4 percent boost holds near 208 all day. A service that reads 208 idle and 200 loaded is a different case: the same unit delivers about 216 volts overnight, and that light-load figure has to stay inside the equipment's upper tolerance.

Third, set the rating from full-load current at 208 volts, totalling whatever runs through the transformer at the same time and taking the next step up from 10, 15, 20, 30, 40, 50 or 60 amps. Phase follows the load, not the service.

Installation notes

A 4 percent correction leaves no room for a careless measurement. Take the reading line to line at the equipment terminals under normal operating load, and take it more than once across a working day. An input that turns out to be 208 rather than 200 produces about 216 volts, and one sitting at 212 produces about 220.

The device is an insulating transformer reconnected as an autotransformer. Input and output share a winding, so the 208 volt output is not isolated from the 200 volt supply, no separately derived system is created, and no neutral is derived. Three-phase corrections normally use two transformers in open delta on a three-wire supply, raising line-to-line voltage only, so the 120 volt line-to-neutral circuits on a 208Y/120 panel are untouched.

Size conductors and overcurrent protection for the actual line current, which is the load current rather than a fraction of it. NEC Article 450 covers transformer overcurrent protection, and 210.9 and 215.11 cover autotransformers supplying branch circuits and feeders; confirm the language in the code cycle your AHJ enforces.

Common questions
Is a 4 percent voltage correction worth making?

It depends entirely on what is connected. A general-purpose motor nameplated 208-230V is rated against 208 volts, and 200 volts sits inside the plus or minus 10 percent band NEMA MG-1 describes, so correcting it buys very little. Equipment with a published input window of plus or minus 5 or 6 percent is a different case, because 200 volts consumes most of that window before any starting dip is added, and such equipment faults rather than derates. Read the stated tolerance first. That number, not the size of the correction, decides whether the correction is worth making.

My equipment lists 208 volts plus or minus 5 percent. Where does 200 volts fall?

Outside it, but only just. A plus or minus 5 percent window on 208 volts runs from about 198 to 218 volts, so a supply measuring 200 sits roughly 2 volts above the bottom. The practical problem is that those 2 volts have to absorb everything else: the drop in the branch circuit feeding the machine, and the dip that occurs whenever another motor on the panel starts. Equipment specified this tightly is usually the equipment that faults, and a correction to 208 puts the operating point back in the middle of the window instead of at its edge.

Can a buck-boost transformer be installed ahead of a variable frequency drive?

Yes, on the drive's input. Size it on the drive's rated input current rather than the motor's full-load amps, since the two differ and drive input current is not sinusoidal, and confirm the corrected voltage stays inside the drive's rated input range at light load as well as under load. A buck-boost transformer must never be connected on the output of a drive, between the drive and the motor, because that output is a switched pulse-width waveform rather than a sine wave. Correcting on the input side also does not isolate the drive, since an autotransformer shares a winding with the supply.

My machine is rated 200 volts and the building is 208. Do I need a correction in the other direction?

Usually not. Equipment rated 200 volts, common on imported machine tools, sees 208 volts as about 4 percent high, well inside the plus or minus 10 percent tolerance a general-purpose motor is built to. A buck connection is worth considering when the machine's documentation states a tighter window, when the service also runs above nominal so the machine sees closer to 218 volts, or when the load is resistive and the extra voltage puts roughly 8 percent more heat into an element than it was sized to dissipate.