Orders accepted now — shipping resumes September 5, 2026 (575) 228-1390contact@xfmrdirect.com (575) 228-1390contact@xfmrdirect.com Request a Quote

205V to 230V Buck-Boost Transformer

A service that reads 208V in the morning and 205V at four in the afternoon is common, and the afternoon reading is the one that matters. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.

2

Load current (amps)

Single-Phase

3.12 amps0.72 kVA · $279.40 · Ships in 2-3 weeks4.35 amps1 kVA · $254.92 · ✔ In Stock: 305 amps1.15 kVA · $280.80 · Ships in 2-3 weeks6.25 amps1.44 kVA · $297.41 · Ships in 2-3 weeks7.81 amps1.8 kVA · $357.77 · ✔ In Stock: 238.7 amps2 kVA · $329.73 · ✔ In Stock: 2310 amps2.3 kVA · $245.01 · ✔ In Stock: 1010.87 amps2.5 kVA · $294.73 · ✔ In Stock: 1010.9 amps2.51 kVA · $373.82 · Ships in 2-3 weeks10.94 amps2.52 kVA · $339.36 · Ships in 5-6 weeks13.04 amps3 kVA · $350.35 · Ships in 2-3 weeks15 amps3.45 kVA · $393.85 · ✔ In Stock: 1915.6 amps3.59 kVA · $505.46 · ✔ In Stock: 1918.6 amps4.28 kVA · $317.84 · Ships in 5-6 weeks20 amps4.6 kVA · $524.24 · ✔ In Stock: 2420.8 amps4.78 kVA · $321.82 · Ships in 5-6 weeks21.74 amps5 kVA · $477.70 · ✔ In Stock: 2422 amps5.06 kVA · $475.41 · ✔ In Stock: 223.4 amps5.39 kVA · $531.56 · ✔ In Stock: 2423.44 amps5.39 kVA · $480.31 · ✔ In Stock: 2425 amps5.75 kVA · $680.28 · ✔ In Stock: 4326.09 amps6 kVA · $621.96 · ✔ In Stock: 2430 amps6.9 kVA · $705.99 · ✔ In Stock: 4331.2 amps7.19 kVA · $707.87 · ✔ In Stock: 4331.25 amps7.19 kVA · $500.41 · ✔ In Stock: 232.61 amps7.5 kVA · $743.66 · ✔ In Stock: 4339.13 amps9 kVA · $567.92 · ✔ In Stock: 640 amps9.2 kVA · $569.85 · ✔ In Stock: 641.67 amps9.58 kVA · $572.05 · ✔ In Stock: 646.9 amps10.79 kVA · $744.27 · ✔ In Stock: 850 amps11.5 kVA · $1,104.87 · ✔ In Stock: 3952.17 amps12 kVA · $758.16 · ✔ In Stock: 860 amps13.8 kVA · $1,150.03 · ✔ In Stock: 3962.5 amps14.4 kVA · $1,155.66 · ✔ In Stock: 3965.22 amps15 kVA · $1,439.05 · ✔ In Stock: 3970 amps16.1 kVA · $1,162.14 · ✔ In Stock: 678.1 amps17.96 kVA · $1,492.81 · Ships in 5-6 weeks80 amps18.4 kVA · $1,193.07 · ✔ In Stock: 686.96 amps20 kVA · $1,193.07 · ✔ In Stock: 690 amps20.7 kVA · $1,660.33 · ✔ In Stock: 293.7 amps21.6 kVA · $1,369.72 · ✔ In Stock: 2100 amps23 kVA · $1,195.67 · Ships in 5-6 weeks104 amps23.92 kVA · $1,200.57 · Ships in 5-6 weeks108.7 amps25 kVA · $1,373.32 · ✔ In Stock: 2125 amps28.75 kVA · $1,206.57 · ✔ In Stock: 4130.43 amps30 kVA · $1,203.32 · ✔ In Stock: 4

Three-Phase Delta

2.51 amps1 kVA · $390.12 · Ships in 2-3 weeks5 amps1.99 kVA · $526.52 · Ships in 2-3 weeks5.02 amps2 kVA · $526.52 · ✔ In Stock: 156.25 amps2.49 kVA · $495.41 · Ships in 5-6 weeks6.28 amps2.5 kVA · $529.15 · Ships in 2-3 weeks7.53 amps3 kVA · $531.80 · Ships in 2-3 weeks10 amps3.98 kVA · $516.27 · ✔ In Stock: 512.5 amps4.98 kVA · $886.93 · Ships in 2-3 weeks12.55 amps5 kVA · $824.64 · Ships in 2-3 weeks13.18 amps5.25 kVA · $576.36 · Ships in 5-6 weeks15 amps5.98 kVA · $845.49 · ✔ In Stock: 915.06 amps6 kVA · $845.78 · ✔ In Stock: 918.8 amps7.49 kVA · $891.43 · Ships in 2-3 weeks18.83 amps7.5 kVA · $1,117.55 · ✔ In Stock: 920 amps7.97 kVA · $1,129.18 · ✔ In Stock: 1220.83 amps8.3 kVA · $845.87 · Ships in 5-6 weeks22.59 amps9 kVA · $1,144.70 · ✔ In Stock: 1225 amps9.96 kVA · $1,204.74 · ✔ In Stock: 2129.17 amps11.62 kVA · $1,195.05 · Ships in 2-3 weeks30 amps11.95 kVA · $1,246.67 · ✔ In Stock: 2130.12 amps12 kVA · $1,247.24 · ✔ In Stock: 2131.25 amps12.45 kVA · $960.29 · ✔ In Stock: 135 amps13.94 kVA · $960.29 · ✔ In Stock: 337.65 amps15 kVA · $1,730.10 · ✔ In Stock: 2140 amps15.93 kVA · $960.90 · ✔ In Stock: 341 amps16.33 kVA · $963.80 · ✔ In Stock: 341.67 amps16.6 kVA · $1,574.64 · Ships in 2-3 weeks46 amps18.33 kVA · $1,774.07 · ✔ In Stock: 446.88 amps18.68 kVA · $1,778.34 · Ships in 5-6 weeks50 amps19.92 kVA · $2,469.23 · ✔ In Stock: 1950.2 amps20 kVA · $1,802.08 · ✔ In Stock: 460 amps23.9 kVA · $2,569.54 · ✔ In Stock: 1962.5 amps24.9 kVA · $1,853.67 · ✔ In Stock: 462.76 amps25 kVA · $2,580.76 · ✔ In Stock: 1970 amps27.89 kVA · $2,802.67 · ✔ In Stock: 375.31 amps30 kVA · $3,206.10 · ✔ In Stock: 1978.1 amps31.11 kVA · $3,221.09 · Ships in 2-3 weeks80 amps31.87 kVA · $2,881.70 · ✔ In Stock: 383.33 amps33.2 kVA · $2,894.11 · ✔ In Stock: 390 amps35.85 kVA · $3,237.20 · ✔ In Stock: 194.13 amps37.5 kVA · $2,503.88 · Ships in 2-3 weeks100 amps39.84 kVA · $2,894.47 · Ships in 5-6 weeks104 amps41.43 kVA · $2,908.94 · Ships in 5-6 weeks125 amps49.8 kVA · $2,923.49 · ✔ In Stock: 2125.51 amps50 kVA · $2,412.19 · ✔ In Stock: 2150 amps59.76 kVA · $3,072.79 · ✔ In Stock: 13200 amps79.67 kVA · $5,787.26 · Ships in 2-3 weeks208 amps82.86 kVA · $5,811.60 · Ships in 2-3 weeks250 amps99.59 kVA · $6,693.27 · ✔ In Stock: 13
Only exact rated-amperage matches that can be purchased online are shown. Without JavaScript, an amperage choice opens its exact product page.
✔ Recommended for your application

Sizing uses the correction winding only. Verify load current against the equipment nameplate and install per the included wiring diagram and applicable NEC requirements.

Quick answer

Measured input
205V
Required output
230V
Correction
Boost (raise voltage) · 12.2%
Size from
System phase and equipment nameplate amps
Technical details

205V to 230V technical overview

A service that reads 208V in the morning and 205V at four in the afternoon is common, and the afternoon reading is the one that matters. A 205V to 230V buck-boost transformer raises the supply about 12.2 percent, putting 230V equipment at nominal voltage while the building is working hardest. Sizing from the best reading of the day is the most frequent mistake in voltage correction work, because equipment does not fail at 8 a.m., it fails at the peak. Choose the correction from what a meter reports under load, not from the number on the panel schedule. Both single-phase and three-phase versions are offered, from 10 to 60 amps.

Where 205V to 230V correction is used

Peak load is the organizing idea here. The buildings that need a 205V input selection are the ones whose demand curve has a sharp afternoon or evening shape, so the voltage they actually run on is several volts below the one recorded during a morning site visit.

  • Schools and campuses, where classroom HVAC, kitchens and shop equipment come on together and the low point falls in the early afternoon.
  • Restaurants and food courts, where cooking equipment, refrigeration and makeup air all run through dinner service.
  • Retail and strip centers in hot climates, where every tenant rooftop unit runs at once on a summer afternoon.
  • Ice rinks, indoor pools and controlled environment agriculture with concentrated, scheduled loads.
  • Agricultural and irrigation services where pumping is seasonal and largely simultaneous.

In each case the equipment nameplate says 230V, the panel schedule says 208V, and the only reading that explains the service calls is the one nobody took: phase-to-phase voltage at the disconnect while everything in the building is running.

Why this 205V to 230V voltage pair matters

At 205V a 230V motor is running about 11 percent below nameplate, just outside the plus or minus 10 percent NEMA MG-1 permits. That is the specific problem this correction solves, and it is one nobody upstream is obliged to fix, because 205V remains inside the Range A service window ANSI C84.1 defines for a 208V nominal system.

Timing makes it worse than the raw numbers suggest. The lowest voltage of the day usually coincides with the highest ambient temperature, so a motor already drawing extra current because of undervoltage is trying to shed that additional heat into hot air in a hot mechanical room. The result is the familiar pattern where a rooftop unit or compressor trips on overload only on the hottest afternoons, then tests perfectly the next morning when the technician arrives with a meter.

Installation notes

Sizing guidance

Log the voltage rather than spot-checking it. A recording meter left on the service for a working week, or the voltage history already stored by a variable frequency drive or smart starter, gives the range the correction has to work across. A single reading taken during a site visit is the least useful data available.

Select the input from the low end of that range, where the equipment is actually failing, then check the consequence at the high end. A 205 to 230 configuration fed 210V delivers about 236V, which is comfortable for 230V equipment, so the correction holds across the whole range instead of trading one problem for another.

Amperage comes from the load. Use nameplate full-load amps or measured running current, whichever is higher, and select among the 10, 15, 20, 30, 40, 50 and 60 amp ratings above that figure. Phase configuration matches the equipment, either three-phase or single-phase across two legs of the 208Y/120 service.

Installation notes

Document the input voltage range before and after the work. The value of a 205V input selection rests entirely on the measurement behind it, and a before-and-after record taken at the equipment disconnect is what settles later arguments about whether the correction did its job.

Understand what is being installed. A buck-boost transformer is an insulating transformer reconnected as an autotransformer, which means the output is not isolated from the input and shares its grounding reference. Three-phase corrections are wired open-delta with two coils, correcting the phase-to-phase voltages only. No neutral is created, so a 3-wire boosted circuit stays 3-wire and every 120V load remains on the original 208Y/120 panel.

Size conductors and overcurrent protection to the branch-circuit rules and NEC Article 450, mount the unit where ambient temperature stays within its rating, and have a licensed electrician verify the connection against the unit diagram before energizing.

Common questions
How do I confirm that my service is really 205V?

Measure phase to phase at the equipment disconnect with the building under its normal working load, and repeat the measurement during the busiest hour of the day. A recording meter left in place for a week is better still. Panel schedules and one-line drawings show nominal values, not delivered voltage, and a morning reading on a lightly loaded building typically overstates what the equipment actually receives.

Why does building voltage drop in the afternoon?

Voltage drop is proportional to current, so the more load a building and its utility feeder carry, the lower the delivered voltage. On a summer afternoon, air conditioning across an entire feeder runs at once, current rises through the service conductors and the utility transformer, and phase-to-phase voltage at the panel falls by several volts compared with an early morning reading on the same equipment.

My voltage swings between 205V and 210V. Which input should I choose?

Choose the input that matches the low end, where the equipment is failing, then verify the high end is acceptable. A correction from 205V to 230V is a ratio of about 1.12, so a 210V input produces roughly 236V, which stays within tolerance for 230V and 240V equipment. Selecting for the high end instead would leave the load undervoltage at exactly the hours when it matters.

Does a buck-boost transformer regulate or stabilize voltage?

No. A buck-boost transformer is a fixed-ratio device, not a voltage regulator. It multiplies whatever it receives by a constant ratio, so variation on the supply passes through to the load in proportion. Correcting a persistent offset between supply and nameplate is what it does well, while smoothing a fluctuating or unstable supply requires a voltage regulator or line conditioner.