Orders accepted now — shipping resumes September 5, 2026 (575) 228-1390contact@xfmrdirect.com (575) 228-1390contact@xfmrdirect.com Request a Quote

215V to 230V Buck-Boost Transformer

Most 215V complaints are starting complaints. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.

2

Load current (amps)

Single-Phase

4.35 amps1 kVA · $296.91 · Ships in 2-3 weeks5 amps1.15 kVA · $300.26 · Ships in 2-3 weeks8.7 amps2 kVA · $302.83 · ✔ In Stock: 309.38 amps2.16 kVA · $331.09 · ✔ In Stock: 3010 amps2.3 kVA · $315.87 · Ships in 2-3 weeks10.87 amps2.5 kVA · $350.68 · ✔ In Stock: 3013.04 amps3 kVA · $323.52 · ✔ In Stock: 2315 amps3.45 kVA · $329.99 · ✔ In Stock: 2320 amps4.6 kVA · $399.98 · Ships in 2-3 weeks21.74 amps5 kVA · $403.15 · ✔ In Stock: 1925 amps5.75 kVA · $412.76 · ✔ In Stock: 1926.09 amps6 kVA · $416.46 · ✔ In Stock: 1930 amps6.9 kVA · $424.76 · ✔ In Stock: 1932.61 amps7.5 kVA · $546.53 · ✔ In Stock: 2434.7 amps7.98 kVA · $552.19 · ✔ In Stock: 2439.13 amps9 kVA · $562.57 · ✔ In Stock: 2440 amps9.2 kVA · $564.32 · ✔ In Stock: 2446.88 amps10.78 kVA · $573.27 · ✔ In Stock: 2450 amps11.5 kVA · $593.94 · ✔ In Stock: 4352.17 amps12 kVA · $757.23 · ✔ In Stock: 4360 amps13.8 kVA · $607.72 · ✔ In Stock: 4362.5 amps14.38 kVA · $609.07 · ✔ In Stock: 4365.22 amps15 kVA · $698.40 · ✔ In Stock: 4370 amps16.1 kVA · $708.76 · ✔ In Stock: 178.1 amps17.96 kVA · $723.55 · ✔ In Stock: 180 amps18.4 kVA · $726.43 · ✔ In Stock: 186.96 amps20 kVA · $921.35 · ✔ In Stock: 190 amps20.7 kVA · $736.20 · ✔ In Stock: 1108.7 amps25 kVA · $1,246.33 · ✔ In Stock: 39130.43 amps30 kVA · $1,399.92 · ✔ In Stock: 39163.04 amps37.5 kVA · $1,781.75 · ✔ In Stock: 2217.39 amps50 kVA · $1,381.14 · ✔ In Stock: 2

Three-Phase Delta

2.51 amps1 kVA · $348.24 · Ships in 2-3 weeks5 amps1.99 kVA · $350.05 · Ships in 2-3 weeks5.02 amps2 kVA · $350.05 · Ships in 2-3 weeks6.28 amps2.5 kVA · $351.80 · ✔ In Stock: 157.53 amps3 kVA · $465.22 · ✔ In Stock: 1510 amps3.98 kVA · $472.44 · Ships in 2-3 weeks12.55 amps5 kVA · $474.80 · ✔ In Stock: 1115 amps5.98 kVA · $474.80 · ✔ In Stock: 1115.06 amps6 kVA · $475.00 · ✔ In Stock: 1118.83 amps7.5 kVA · $619.82 · Ships in 2-3 weeks20 amps7.97 kVA · $626.42 · Ships in 2-3 weeks21.88 amps8.72 kVA · $753.31 · Ships in 5-6 weeks22.59 amps9 kVA · $725.45 · ✔ In Stock: 925 amps9.96 kVA · $739.00 · ✔ In Stock: 930 amps11.95 kVA · $758.55 · ✔ In Stock: 930.12 amps12 kVA · $758.82 · ✔ In Stock: 931.25 amps12.45 kVA · $760.47 · ✔ In Stock: 934.7 amps13.82 kVA · $993.01 · ✔ In Stock: 1237.65 amps15 kVA · $1,011.79 · ✔ In Stock: 1240 amps15.93 kVA · $1,022.66 · ✔ In Stock: 1250 amps19.92 kVA · $1,229.84 · ✔ In Stock: 2150.2 amps20 kVA · $1,090.84 · ✔ In Stock: 2160 amps23.9 kVA · $1,240.25 · ✔ In Stock: 2162.76 amps25 kVA · $1,243.83 · ✔ In Stock: 2170 amps27.89 kVA · $1,697.10 · Ships in 2-3 weeks75.31 amps30 kVA · $1,551.20 · Ships in 2-3 weeks78.1 amps31.11 kVA · $1,729.92 · Ships in 2-3 weeks80 amps31.87 kVA · $1,736.61 · Ships in 2-3 weeks90 amps35.85 kVA · $1,763.62 · Ships in 2-3 weeks93.75 amps37.35 kVA · $1,768.55 · Ships in 5-6 weeks94.13 amps37.5 kVA · $1,595.68 · ✔ In Stock: 19125.51 amps50 kVA · $2,566.75 · ✔ In Stock: 19188.27 amps75 kVA · $2,755.07 · ✔ In Stock: 1
Only exact rated-amperage matches that can be purchased online are shown. Without JavaScript, an amperage choice opens its exact product page.
✔ Recommended for your application

Sizing uses the correction winding only. Verify load current against the equipment nameplate and install per the included wiring diagram and applicable NEC requirements.

Quick answer

Measured input
215V
Required output
230V
Correction
Boost (raise voltage) · 7.0%
Size from
System phase and equipment nameplate amps
Technical details

215V to 230V technical overview

Most 215V complaints are starting complaints. Equipment that runs acceptably once it is up to speed hums, stalls or drops out when it tries to start on a hot afternoon, because starting is when the circuit is weakest and the motor needs the most. A 215V to 230V buck-boost transformer adds 15 volts, a boost of about 7%, and puts a 230V nameplate load back on its rating with margin for inrush. 230V is the standard NEMA motor nameplate voltage for a 240V distribution system, which is why this pair comes up so often. Single-phase and three-phase, in 10, 15, 20, 30, 40, 50 and 60 amp selections.

Where 215V to 230V correction is used

The loads that produce this pair have high starting current relative to what the circuit can deliver, and they usually cycle. Common examples:

  • Refrigeration and walk-in condensing units that restart against head pressure, which is the hardest start a compressor ever makes and always happens at the worst time of day.
  • Well pumps, booster pumps and irrigation sets that cycle on pressure switches dozens of times per shift.
  • Shop air compressors that unload and reload while the rest of the building is at peak demand.
  • Hydraulic power units, dust collectors, car wash equipment, grain augers and commercial laundry extractors.
  • Elevator and lift hydraulic pumps in older buildings where the run to the machine room is long.

What ties them together is that the fault is intermittent and load dependent. A contractor measures 228V at 9am, finds nothing wrong, and gets called back the following week when production is running and the same circuit reads 215V.

Why this 215V to 230V voltage pair matters

215V is about 6.5% below a 230V nameplate, inside the plus or minus 10% band NEMA MG-1 allows but with most of the margin already spent before the motor draws locked-rotor current. That is the part people miss. Starting current is typically five to seven times full-load amps, and it produces a momentary dip on top of whatever the circuit is already losing, so a terminal resting at 215V can sit well below 200V for the duration of the start. Motor torque follows the square of applied voltage, so 215V instead of 230V gives up roughly 13% of starting and breakdown torque exactly when it is needed. The consequences accumulate: longer acceleration, more time at locked-rotor current, more heat in the windings, and overload relays that trip on the fourth start of the afternoon rather than the first.

Installation notes

Sizing guidance

Measure at the line side of the starter with the machine working, and if the complaint is intermittent, log for a full 24 hours rather than trusting a single reading. A meter that samples once per second will show the sag that a handheld reading during a quiet hour never catches.

Select amperage from the motor nameplate full-load amps, not from the breaker size and not from the NEC table value used for conductor sizing. Add 25% for continuous operation and round up to the next offered amperage among 10, 15, 20, 30, 40, 50 and 60. Where several motors share a panel, decide whether to correct each machine individually or correct at the panel using the sum of the running currents.

Starting current does not drive the selection. Because a buck-boost transformer processes only the difference between input and output, its rating is a small fraction of the motor it supports, and inrush passes through as a brief overload the same way it does through the rest of the circuit.

Installation notes

One step is specific to motor circuits and easy to skip. After the correction is energized, the motor draws less running current than it did at 215V, so verify that the overload relay setting or heater selection still matches the motor's actual current at the corrected voltage. An overload left set for the undervoltage condition no longer protects the way it was intended to.

The transformer itself is an insulating transformer reconnected as an autotransformer, so the output is not isolated from the input and the circuit's grounding reference is unchanged. Three-phase corrections use two units in open delta, correcting phase-to-phase voltage and deriving no neutral. Confirm rotation before returning a three-phase machine to service. Size conductors and overcurrent protection per NEC Article 450 and the branch-circuit rules, and take a final voltage reading at the motor terminals while it is running under load.

Common questions
What is the minimum voltage for a 230V motor?

NEMA MG-1 permits general-purpose motors to operate at plus or minus 10% of nameplate voltage, which puts the low limit for a 230V motor at 207V. Operating there is permitted, not recommended: at the bottom of that range the motor draws more current for the same shaft load, runs hotter, and produces roughly 19% less starting torque than it does at nameplate, because torque varies with the square of applied voltage.

Why does my motor only trip when it starts?

Because starting current is typically five to seven times full-load amps, and that current produces a voltage dip on top of whatever the circuit is already losing. A supply resting at 215V can fall well below 200V during the start, and reduced voltage means reduced torque, which means a longer acceleration at high current. The motor spends more time drawing locked-rotor current, and the overload relay eventually responds to the accumulated heat.

Where should I measure voltage on a motor circuit?

At the line side of the motor starter or at the motor terminals, with the machine running under its normal load. A reading taken at the panel misses everything the branch circuit loses, and a reading taken at an idle disconnect misses everything, since voltage drop only exists when current flows. For intermittent complaints, log voltage across a full working day rather than taking a spot reading.

Will boosting from 215V to 230V reduce motor current?

Yes, on the motor side. A motor driving a fixed mechanical load draws roughly constant power, so raising the terminal voltage about 7% lowers the running current by a similar proportion. Current drawn from the 215V supply ahead of the transformer is slightly higher than the motor current, because the power has to come from somewhere, which is why the input conductors and overcurrent protection are sized for the input side of a boost connection.