Orders accepted now — shipping resumes September 5, 2026 (575) 228-1390contact@xfmrdirect.com (575) 228-1390contact@xfmrdirect.com Request a Quote

220V to 242V Buck-Boost Transformer

Voltage drop is a function of current, conductor size and distance, and no transformer changes that arithmetic. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.

2

Load current (amps)

Single-Phase

4.13 amps1 kVA · $227.99 · Ships in 2-3 weeks4.17 amps1.01 kVA · $228.02 · Ships in 2-3 weeks5 amps1.21 kVA · $228.02 · Ships in 2-3 weeks6.25 amps1.51 kVA · $229.16 · Ships in 2-3 weeks8.26 amps2 kVA · $242.63 · Ships in 2-3 weeks8.33 amps2.02 kVA · $242.72 · Ships in 2-3 weeks10 amps2.42 kVA · $249.71 · ✔ In Stock: 1010.33 amps2.5 kVA · $249.62 · ✔ In Stock: 1012.4 amps3 kVA · $296.77 · Ships in 2-3 weeks15 amps3.63 kVA · $303.68 · Ships in 2-3 weeks20 amps4.84 kVA · $304.35 · Ships in 2-3 weeks20.66 amps5 kVA · $305.14 · Ships in 2-3 weeks20.8 amps5.04 kVA · $305.20 · Ships in 5-6 weeks24.79 amps6 kVA · $441.48 · ✔ In Stock: 225 amps6.05 kVA · $442.12 · ✔ In Stock: 230 amps7.26 kVA · $453.61 · ✔ In Stock: 230.99 amps7.5 kVA · $454.60 · ✔ In Stock: 231.2 amps7.56 kVA · $454.68 · ✔ In Stock: 237.19 amps9 kVA · $454.68 · ✔ In Stock: 640 amps9.68 kVA · $455.16 · ✔ In Stock: 641.7 amps10.1 kVA · $456.95 · ✔ In Stock: 649.59 amps12 kVA · $533.46 · ✔ In Stock: 850 amps12.1 kVA · $534.23 · ✔ In Stock: 860 amps14.52 kVA · $548.21 · ✔ In Stock: 861.98 amps15 kVA · $549.46 · ✔ In Stock: 862.5 amps15.1 kVA · $549.59 · ✔ In Stock: 870 amps16.94 kVA · $719.52 · ✔ In Stock: 680 amps19.36 kVA · $739.48 · ✔ In Stock: 682.64 amps20 kVA · $742.04 · ✔ In Stock: 683.3 amps20.1 kVA · $742.30 · ✔ In Stock: 690 amps21.78 kVA · $1,025.76 · Ships in 2-3 weeks100 amps24.2 kVA · $1,055.77 · Ships in 2-3 weeks103.31 amps25 kVA · $1,060.79 · Ships in 2-3 weeks104 amps25.17 kVA · $1,061.18 · Ships in 2-3 weeks123.97 amps30 kVA · $1,065.79 · ✔ In Stock: 4125 amps30.2 kVA · $1,066.48 · ✔ In Stock: 4

Three-Phase Delta

2.39 amps1 kVA · $277.46 · Ships in 2-3 weeks4.17 amps1.75 kVA · $278.84 · Ships in 2-3 weeks4.77 amps2 kVA · $363.63 · Ships in 2-3 weeks5 amps2.1 kVA · $366.52 · Ships in 2-3 weeks5.96 amps2.5 kVA · $374.40 · Ships in 2-3 weeks6.25 amps2.62 kVA · $374.46 · Ships in 2-3 weeks7.16 amps3 kVA · $374.46 · Ships in 2-3 weeks8.33 amps3.5 kVA · $376.34 · Ships in 2-3 weeks10 amps4.19 kVA · $378.22 · ✔ In Stock: 511.93 amps5 kVA · $483.50 · Ships in 2-3 weeks14.31 amps6 kVA · $498.13 · Ships in 2-3 weeks15 amps6.29 kVA · $498.67 · Ships in 2-3 weeks17.89 amps7.5 kVA · $590.51 · Ships in 2-3 weeks20 amps8.38 kVA · $600.53 · Ships in 2-3 weeks20.8 amps8.74 kVA · $602.76 · Ships in 2-3 weeks21.47 amps9 kVA · $768.67 · Ships in 2-3 weeks25 amps10.48 kVA · $791.42 · ✔ In Stock: 128.63 amps12 kVA · $808.48 · ✔ In Stock: 130 amps12.57 kVA · $812.57 · ✔ In Stock: 131.2 amps13.08 kVA · $1,795.36 · Ships in 2-3 weeks31.3 amps13.1 kVA · $814.12 · ✔ In Stock: 135.79 amps15 kVA · $866.81 · ✔ In Stock: 340 amps16.77 kVA · $885.31 · ✔ In Stock: 341.7 amps17.5 kVA · $889.45 · ✔ In Stock: 347.71 amps20 kVA · $1,218.26 · ✔ In Stock: 450 amps20.96 kVA · $1,228.63 · ✔ In Stock: 459.64 amps25 kVA · $1,260.81 · ✔ In Stock: 460 amps25.15 kVA · $1,261.53 · ✔ In Stock: 462.5 amps26.2 kVA · $1,264.76 · ✔ In Stock: 470 amps29.34 kVA · $1,779.84 · ✔ In Stock: 371.57 amps30 kVA · $1,789.60 · ✔ In Stock: 380 amps33.53 kVA · $1,829.29 · ✔ In Stock: 383.3 amps34.9 kVA · $1,835.45 · ✔ In Stock: 389.47 amps37.5 kVA · $2,228.16 · ✔ In Stock: 390 amps37.72 kVA · $4,164.96 · Ships in 2-3 weeks100 amps41.92 kVA · $4,284.10 · Ships in 2-3 weeks104 amps43.59 kVA · $4,305.57 · Ships in 2-3 weeks119.29 amps50 kVA · $2,290.86 · ✔ In Stock: 2125 amps52.4 kVA · $2,302.31 · ✔ In Stock: 2
Only exact rated-amperage matches that can be purchased online are shown. Without JavaScript, an amperage choice opens its exact product page.
✔ Recommended for your application

Sizing uses the correction winding only. Verify load current against the equipment nameplate and install per the included wiring diagram and applicable NEC requirements.

Quick answer

Measured input
220V
Required output
242V
Correction
Boost (raise voltage) · 10.0%
Size from
System phase and equipment nameplate amps
Technical details

220V to 242V technical overview

Voltage drop is a function of current, conductor size and distance, and no transformer changes that arithmetic. What a 220V to 242V buck-boost transformer does is start the circuit higher so the far end still lands where the equipment needs it. At 10%, this is the largest of the standard corrections in the 240V family, and it is chosen when there is a long run, a heavily loaded feeder, or both, downstream of the correction point. Single-phase and three-phase configurations are available in 10, 15, 20, 30, 40, 50 and 60 amp selections.

Where 220V to 242V correction is used

Distance and load are what put a site on this pair. It shows up on irrigation pump panels and grain handling at the back of a farmstead, quarry and aggregate equipment fed from a yard panel, sawmills and outdoor conveyor runs, remote well fields and lift stations, marina dock pedestals, gate operators and site lighting hundreds of feet from the nearest source, and temporary construction power feeding hoists, welders and material lifts from a service that moves as the job progresses.

It also shows up in buildings where the geometry is simply unfavorable: the utility transformer sits at one property line, the service equipment at another, and the load at the far end of a third run. Nobody made a mistake, the distances just add up.

The tell is a complaint that changes with position rather than with time. If the machine next to the panel is fine and the identical machine at the end of the run is not, the problem is drop along the run, and starting that run at 242 instead of 220 is the direct answer.

Why this 220V to 242V voltage pair matters

242V is chosen because it sits inside the accepted band with room to spend. ANSI C84.1 puts Range A service voltage for a nominal 240V system between 228V and 252V, with a utilization floor of 216V, so a circuit beginning at 242V has roughly 26 volts of drop available before the load falls below that floor. A circuit beginning at 220V has four. The informational notes to NEC 210.19(A) recommend holding branch-circuit drop near 3% and total drop across feeder and branch near 5%, and those are recommendations rather than enforceable limits, but they describe the budget a long run has to fit inside.

Without the correction, the failure is positional and stubborn. The near end of the feeder works, the far end trips overloads on hot afternoons, and every voltage reading taken at the panel says the supply is fine. Boosting the source end gives the run something to lose.

Installation notes

Sizing guidance

Take two measurements, not one: voltage at the panel and voltage at the equipment, recorded at the same moment with the load running. The difference between them is the drop the circuit is actually producing, and it is the number that tells you whether 242 is the right target or whether the conductors are the real problem. A run dropping 8% or more is a conductor sizing issue first, and a buck-boost transformer applied on top of undersized wire corrects the symptom while the conductors keep heating.

Amperage selection follows the correction point. Correcting one machine means sizing on that machine's full-load current. Correcting at the panel means sizing on the total running current of everything downstream, since the transformer carries the whole feeder. Add 25% for continuous loads, then round up to the next offered value among 10, 15, 20, 30, 40, 50 and 60 amps. Phase follows the load: three-phase equipment takes the three-phase configuration, which uses two units in open delta.

Installation notes

Everything downstream of the correction sees the boosted voltage, including loads that were never the complaint. At light load, when the run carries almost no current and drops almost nothing, the far end will sit close to 242V. That is inside the ANSI C84.1 Range A ceiling of 252V for a 240V system and inside the plus or minus 10% window NEMA MG-1 allows a 240V motor, but it is worth confirming that contactor coils, electronics and any 240V lighting on the same circuit are comfortable there.

The device itself is an insulating transformer reconnected as an autotransformer, so input and output are not isolated. Three-phase corrections are open delta and derive no neutral, so a 3-wire source stays 3-wire. Size conductors and overcurrent protection per NEC Article 450 and the branch-circuit rules, allowing for input current higher than output current on a boost, and reverify voltage at both ends after energizing.

Common questions
Why boost to 242V instead of 240V?

Because the target is the voltage at the far end of the run, not at the transformer. 242V is 1% above nominal and well inside the 252V Range A ceiling ANSI C84.1 sets for a 240V system, which leaves headroom to absorb the drop along a long or heavily loaded circuit. Aiming at exactly 240V at the source means the load at the end of the run still arrives low.

How much voltage drop is acceptable on a branch circuit?

The informational notes to NEC 210.19(A) recommend limiting branch-circuit voltage drop to about 3% and total drop across the feeder and branch circuit combined to about 5%. These are recommendations for reasonable operation and efficiency rather than enforceable requirements in those sections. ANSI C84.1 sets the wider practical boundary, with a utilization voltage floor of 216V on a nominal 240V system.

Should the buck-boost transformer go at the panel or at the equipment?

Electrically the result is nearly the same either way, because a buck-boost transformer multiplies whatever it receives by a fixed ratio. The practical difference is scope. Installed at the panel it lifts everything on that feeder, which is efficient when the whole run is low but wrong if some loads on it are already at nominal. Installed at one machine it corrects that machine alone and leaves the rest of the circuit untouched.

Is 242V too high for equipment rated 240V?

No. 242V is about 1% above a 240V nameplate, comfortably inside the plus or minus 10% operating range NEMA MG-1 allows for motors and inside the 252V Range A service voltage ceiling in ANSI C84.1. The caution with a 10% boost is not the target voltage itself but the source: if the supply climbs to 240V overnight, the output climbs to about 264V, so the high end of the supply range should be verified before selecting.