220V to 208V Buck-Boost Transformers
ANSI C84.1 puts the upper limit of Range A service voltage for a 208 volt system at 218 volts. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.
Load current (amps)
Quick answer
- Measured input
- 220V
- Required output
- 208V
- Correction
- Buck (lower voltage) · 5.5%
- Size from
- System phase and equipment nameplate amps
Technical details
220V to 208V technical overview
ANSI C84.1 puts the upper limit of Range A service voltage for a 208 volt system at 218 volts. A reading of 220 is past it, at the edge of the wider Range B, and every 208 volt load in the building is running roughly 6 percent above nameplate. A 220V to 208V buck-boost transformer removes that surplus with a fixed 5.5 percent buck. The pair applies to genuine 220 volt supplies and, more often, to nominal 208 volt services that simply measure 220 at the panel. Single-phase and three-phase, 10 through 60 amps.
Where 220V to 208V correction is used
A 208 volt system reading 220 is usually the result of a supply with more capacity than the building needs.
Utility transformers and their tap settings are chosen for worst-case load at the end of a feeder. A tenant space near the substation, or a building whose connected load never approached the service it was designed with, receives voltage at the top of the band all day. Interior dry-type transformers left on a raised tap after a load change do the same thing.
Two modern causes are worth checking. Facilities with significant on-site solar often see voltage rise during export hours, which is when the reading tends to peak. And spaces built out for heavy equipment that was never installed, or that has since been replaced by lower-draw machines, carry an oversized service against a light load.
The equipment that objects is the 208 volt rated kind: elevator and escalator controllers, LED drivers and lighting ballasts, rack PDUs and UPS units, commercial kitchen equipment, packaged HVAC, and any 208 volt heating element.
Why this 220V to 208V voltage pair matters
Nothing on a 208 volt system fails outright at 220 volts. It degrades.
Motors handle it easily, since 220 falls within the plus or minus 10 percent NEMA MG-1 allows around a 208 volt nameplate, though a lightly loaded motor at high voltage draws more magnetizing current and runs warmer than it needs to. The loads that actually suffer are resistive and electronic.
Resistive first: watts follow the square of voltage, so a 208 volt element at 220 volts dissipates about 12 percent more than its rating, and the thermostats and contactors around it inherit the consequences.
Electronics second: LED drivers, switching power supplies and control boards specified for 208 volts have a limited input window, and steady operation near or above the top of it is what produces the pattern of scattered, hard-to-explain failures across a facility. Stack the transients an incoming line normally carries on top of an already elevated base and there is less margin left every time one arrives.
Installation notes
Sizing guidance
Confirm what you actually have first. Measure line to line at the panel or disconnect that will feed the transformer, more than once, at both busy and quiet times. A genuine 220 volt system reads near 220 regardless of building load, while a nominal 208 volt service running high tends to sag when large loads start. If the reading swings, select against the voltage present for most operating hours, because this is a fixed-ratio device rather than a regulator.
Phase follows the load. Amperage follows the load full-load current at 208 volts, summed for everything on the corrected circuit and rounded up to the next available step of 10, 15, 20, 30, 40, 50 or 60 amps. Breaker rating is not a proxy for load current, particularly on motor circuits.
Because only the 12 volt difference passes through the transformer windings, the unit processes about 6 percent of the load apparent power, so a physically small transformer serves a large load.
Installation notes
On a 208Y/120 system, be specific about what is being corrected. A buck-boost transformer connected to a three-wire feed changes line-to-line voltage only. It does not carry a neutral, does not derive one, and leaves the 120 volt line-to-neutral circuits exactly where they were. If the panel also runs high on its 120 volt circuits, that is a separate problem with a separate answer.
The device is an insulating transformer reconnected as an autotransformer, so input and output share a conductive path. The connection provides no isolation and creates no separately derived system. Three-phase corrections normally use two transformers in open delta, which is why a three-wire source stays a three-wire source on the load side.
Size conductors and overcurrent protection to the NEC using the actual current at each connection, and re-verify voltage at the equipment once the correction is energized with normal load running. XFMR Direct sells buck-boost transformers from multiple manufacturers.
Common questions
- Is 220 volts too high for 208 volt equipment?
220 volts is 5.8 percent above a 208 volt nameplate. For motors that is inside the plus or minus 10 percent NEMA MG-1 permits. For resistive and electronic loads it matters more: a 208 volt heating element on 220 volts produces about 12 percent more heat than rated, and 208 volt power supplies and LED drivers have narrower input windows than motors do. It also exceeds the 218 volt Range A service limit ANSI C84.1 sets for a 208 volt system.
- Why is my 208 volt service reading 220 volts?
The usual reason is a lightly loaded supply. Utility transformer taps are set so the far end of a feeder stays acceptable at peak load, so a building close to the source, or one drawing far less than its service was sized for, sits near the top of the band. Interior transformers left on a raised tap and on-site solar export can each add to it. Measuring at several times of day usually identifies which.
- Will a 220 to 208 volt buck-boost transformer fix my 120 volt circuits too?
No. On a 208Y/120 system a buck-boost transformer corrects line-to-line voltage only. It does not carry or create a neutral, so the 120 volt line-to-neutral circuits are unchanged by it. If those circuits are also high, the correction has to be made where they originate rather than downstream of the panel.
- Can I use this to make 208 volts from a 240 volt supply?
Not with this pair, because the ratio is wrong. 240 to 208 volts is a 13 percent reduction against the 5.5 percent this correction makes, so a 220 to 208 volt unit fed 240 volts delivers roughly 227 volts. A buck-boost transformer is fixed ratio, so select the correction matching the voltage your meter reads at the connection point.