196V to 208V Buck-Boost Transformers

196 volts on a 208 volt system is almost always a loaded reading. Choose the system phase and equipment nameplate amps below to see an available, buyable unit.

2

Load current (amps)

Single-Phase

4.81 amps1 kVA · $264.98 · Ships in 2-3 weeks5 amps1.04 kVA · $265.89 · Ships in 2-3 weeks6.25 amps1.3 kVA · $269.74 · Ships in 2-3 weeks8.33 amps1.73 kVA · $265.22 · Ships in 2-3 weeks9.38 amps1.95 kVA · $271.08 · ✔ In Stock: 309.62 amps2 kVA · $271.84 · ✔ In Stock: 3010 amps2.08 kVA · $274.77 · Ships in 2-3 weeks12.02 amps2.5 kVA · $236.68 · ✔ In Stock: 3012.5 amps2.6 kVA · $287.12 · Ships in 2-3 weeks14.42 amps3 kVA · $291.23 · Ships in 2-3 weeks15 amps3.12 kVA · $293.89 · ✔ In Stock: 2315.6 amps3.24 kVA · $295.40 · ✔ In Stock: 2316.7 amps3.47 kVA · $282.31 · Ships in 2-3 weeks20 amps4.16 kVA · $288.88 · ✔ In Stock: 1020.83 amps4.33 kVA · $290.45 · ✔ In Stock: 1021.9 amps4.56 kVA · $360.89 · Ships in 2-3 weeks24.04 amps5 kVA · $410.89 · ✔ In Stock: 1025 amps5.2 kVA · $367.76 · ✔ In Stock: 1926.6 amps5.53 kVA · $418.72 · Ships in 2-3 weeks28.85 amps6 kVA · $377.26 · ✔ In Stock: 1929.2 amps6.07 kVA · $423.35 · Ships in 2-3 weeks30 amps6.24 kVA · $379.11 · ✔ In Stock: 1931.25 amps6.5 kVA · $380.22 · ✔ In Stock: 1936.06 amps7.5 kVA · $495.42 · ✔ In Stock: 1940 amps8.32 kVA · $504.15 · ✔ In Stock: 2441.67 amps8.67 kVA · $425.55 · Ships in 5-6 weeks43.27 amps9 kVA · $509.73 · ✔ In Stock: 2446.9 amps9.76 kVA · $513.17 · ✔ In Stock: 2450 amps10.4 kVA · $770.98 · ✔ In Stock: 4357.69 amps12 kVA · $797.38 · ✔ In Stock: 2460 amps12.48 kVA · $802.55 · ✔ In Stock: 4362.5 amps13 kVA · $805.65 · ✔ In Stock: 4370 amps14.56 kVA · $708.95 · ✔ In Stock: 672.12 amps15 kVA · $940.14 · ✔ In Stock: 4378.1 amps16.24 kVA · $670.71 · ✔ In Stock: 180 amps16.64 kVA · $728.61 · ✔ In Stock: 683.3 amps17.33 kVA · $731.38 · ✔ In Stock: 690 amps18.72 kVA · $843.27 · ✔ In Stock: 893.8 amps19.51 kVA · $973.83 · ✔ In Stock: 196.15 amps20 kVA · $853.53 · ✔ In Stock: 6120.19 amps25 kVA · $1,154.28 · ✔ In Stock: 39125 amps26 kVA · $1,158.48 · ✔ In Stock: 39144.23 amps30 kVA · $1,632.91 · ✔ In Stock: 39150 amps31.2 kVA · $1,647.69 · Ships in 2-3 weeks156 amps32.45 kVA · $1,656.16 · Ships in 2-3 weeks167 amps34.74 kVA · $1,194.04 · ✔ In Stock: 6180.29 amps37.5 kVA · $1,650.08 · ✔ In Stock: 6188 amps39.1 kVA · $1,369.12 · ✔ In Stock: 2200 amps41.6 kVA · $1,698.16 · Ships in 2-3 weeks208 amps43.26 kVA · $1,706.99 · Ships in 2-3 weeks240.38 amps50 kVA · $1,371.37 · ✔ In Stock: 2250 amps52 kVA · $1,715.52 · ✔ In Stock: 4

Three-Phase Delta

2.78 amps1 kVA · $312.42 · Ships in 2-3 weeks5 amps1.8 kVA · $312.42 · Ships in 2-3 weeks5.55 amps2 kVA · $312.42 · Ships in 2-3 weeks6.25 amps2.25 kVA · $313.98 · Ships in 2-3 weeks6.94 amps2.5 kVA · $404.24 · Ships in 2-3 weeks8.33 amps3 kVA · $416.74 · ✔ In Stock: 159.38 amps3.38 kVA · $421.65 · ✔ In Stock: 1510 amps3.6 kVA · $421.65 · Ships in 2-3 weeks12.5 amps4.51 kVA · $423.76 · Ships in 2-3 weeks13.88 amps5 kVA · $423.76 · Ships in 2-3 weeks15 amps5.4 kVA · $423.76 · ✔ In Stock: 1115.6 amps5.63 kVA · $425.88 · ✔ In Stock: 1116.65 amps6 kVA · $535.88 · ✔ In Stock: 1116.7 amps6.01 kVA · $586.36 · Ships in 2-3 weeks20 amps7.21 kVA · $586.36 · ✔ In Stock: 520.82 amps7.5 kVA · $449.07 · ✔ In Stock: 1120.83 amps7.5 kVA · $589.29 · ✔ In Stock: 521.9 amps7.89 kVA · $561.51 · Ships in 2-3 weeks24.98 amps9 kVA · $760.28 · ✔ In Stock: 525 amps9.01 kVA · $656.38 · ✔ In Stock: 929.2 amps10.5 kVA · $776.97 · Ships in 2-3 weeks30 amps10.81 kVA · $676.63 · ✔ In Stock: 931.3 amps11.3 kVA · $678.72 · ✔ In Stock: 933.31 amps12 kVA · $871.99 · ✔ In Stock: 940 amps14.41 kVA · $900.53 · ✔ In Stock: 1241.64 amps15 kVA · $905.94 · ✔ In Stock: 1241.67 amps15.01 kVA · $804.63 · Ships in 5-6 weeks46.9 amps16.9 kVA · $916.71 · ✔ In Stock: 1250 amps18.01 kVA · $958.43 · ✔ In Stock: 2155.51 amps20 kVA · $983.51 · ✔ In Stock: 1260 amps21.62 kVA · $997.68 · ✔ In Stock: 2162.5 amps22.5 kVA · $1,001.53 · ✔ In Stock: 2169.39 amps25 kVA · $3,072.83 · ✔ In Stock: 2170 amps25.22 kVA · $1,223.73 · ✔ In Stock: 378.1 amps28.14 kVA · $1,116.23 · Ships in 2-3 weeks80 amps28.82 kVA · $1,257.67 · ✔ In Stock: 383.27 amps30 kVA · $1,127.29 · ✔ In Stock: 2183.33 amps30.02 kVA · $1,262.51 · ✔ In Stock: 390 amps32.42 kVA · $1,632.96 · ✔ In Stock: 493.8 amps33.8 kVA · $3,205.28 · Ships in 2-3 weeks100 amps36.03 kVA · $4,451.37 · ✔ In Stock: 19104.09 amps37.5 kVA · $1,675.52 · ✔ In Stock: 4125 amps45 kVA · $4,651.55 · ✔ In Stock: 19138.79 amps50 kVA · $5,661.60 · ✔ In Stock: 19150 amps54.04 kVA · $5,776.03 · Ships in 2-3 weeks156 amps56.2 kVA · $5,805.69 · Ships in 2-3 weeks167 amps60 kVA · $1,828.64 · ✔ In Stock: 3188 amps67.73 kVA · $2,751.16 · ✔ In Stock: 1200 amps72.05 kVA · $2,270.39 · Ships in 2-3 weeks208 amps74.94 kVA · $2,282.33 · Ships in 2-3 weeks208.18 amps75 kVA · $2,739.74 · ✔ In Stock: 1250 amps90 kVA · $2,418.34 · ✔ In Stock: 2277.57 amps100 kVA · $2,425.90 · ✔ In Stock: 2
Only exact rated-amperage matches that can be purchased online are shown. Without JavaScript, an amperage choice opens its exact product page.
✔ Recommended for your application

Sizing uses the correction winding only. Verify load current against the equipment nameplate and install per the included wiring diagram and applicable NEC requirements.

Quick answer

Measured input
196V
Required output
208V
Correction
Boost (raise voltage) · 6.1%
Size from
System phase and equipment nameplate amps
Technical details

196V to 208V technical overview

196 volts on a 208 volt system is almost always a loaded reading. Take it at six in the morning and the panel may show 205. Take it while the compressors, the elevator and the kitchen are all working and it settles at 196. A 196V to 208V buck-boost transformer applies about a 6 percent boost to restore nominal under those loaded conditions. The reason this pair matters is that 196 is the voltage the equipment actually experiences while it runs, and the running condition is the one that does the damage. Single-phase and three-phase, 10 through 60 amps.

Where 196V to 208V correction is used

This pair belongs to shared services, where the voltage on your panel depends partly on what the neighbors are doing. It is a load-driven sag rather than a fixed system voltage or a simple conductor-length problem.

Common settings:

  • Strip centers and multi-tenant retail on a common service, where a restaurant's cooking and refrigeration load pulls the building down at dinner
  • Tenant improvements added to a service originally sized for a different occupancy
  • Machine shops where a large press, compressor or oven loads the panel every cycle
  • Mixed-use buildings carrying residential and commercial load on one transformer
  • Laundromats, breweries and commissary kitchens with high simultaneous demand
  • Small server and telecom rooms fed from a shared house panel

The pattern to look for is variability. A legacy 200 volt system reads the same regardless of load. A long-feeder problem tracks the current in one specific circuit. A shared-service sag moves with the whole building, follows the clock rather than your own equipment, and does not correlate with anything you control.

Why this 196V to 208V voltage pair matters

196 volts is 5.8 percent below a 208 volt nominal and just under the ANSI C84.1 Range A service minimum of 197 volts. Being only marginally below is part of the difficulty, because the utility is unlikely to treat it as a defect and the building is left to solve it.

The damage happens in the loaded condition. Equipment on a shared service is running when the voltage is lowest, so it never gets the low-current, low-heat operating point it was designed around. Refrigeration compressors on a 208 volt nameplate draw increased current and reject the extra heat into their own windings, then short-cycle as head pressure and superheat drift away from design. Motor overloads trip in the afternoon and reset by morning, which sends technicians hunting for a fault that is not there. Drives and switching power supplies fault on undervoltage during the additional dip when a large motor elsewhere in the building starts.

Installation notes

Sizing guidance

Take the reading at the worst moment, then check the best one. Measure line to line at the panel during peak building load and again during the lightest load you expect. A buck-boost transformer applies a fixed ratio to whatever it receives, so both ends of the swing move together. A 6 percent boost on a supply ranging from 196 to 205 volts produces roughly 208 to 217, which stays under the 218 volt ANSI Range A upper limit. If the light-load reading is higher than that, choose a smaller correction.

Then decide the scope. Correcting one problem machine is simpler and cheaper. Correcting a subpanel fixes everything behind it and is worth the difference when several loads are affected. Either way, size on load current rather than breaker size: total the full-load amps of what runs simultaneously through the transformer and select the next rating up from 10, 15, 20, 30, 40, 50 or 60 amps. Phase follows the load.

Installation notes

Rule out a fault before correcting a symptom. A panel that sags to 196 under load can be showing a loose lug, a corroded service termination, a failing utility connection or a badly unbalanced three-phase load. Check terminations with a thermal camera while the building is working, compare all three line-to-line readings against each other, and confirm the shortfall is distributed rather than concentrated on one phase. A buck-boost transformer boosts every phase by the same ratio, so it raises the level but does not correct an imbalance between phases.

Once the supply is sound: the unit is an insulating transformer reconnected as an autotransformer, so the output shares a winding with the input, is not isolated from it, and derives no neutral. Three-phase corrections normally use two transformers in open delta on a three-wire supply. Size conductors and overcurrent devices for the full load current, follow NEC Article 450 for transformer protection and 210.9 or 215.11 for autotransformers supplying branch circuits and feeders, and verify with the AHJ.

Common questions
When should I take the voltage reading used to select a buck-boost transformer?

Take it while the building is at its heaviest normal load, measured line to line at the panel or equipment that has the problem, and take a second reading at the lightest load you expect. On a shared service the voltage moves with total building demand, so a morning reading can be ten volts higher than an afternoon one. Buck-boost transformers apply a fixed ratio, so the correction has to suit the whole measured range, not one point in it.

Will boosting from 196 to 208 volts push my voltage too high at light load?

It depends on how far the supply recovers. A 6 percent boost raises a 205 volt light-load reading to about 217 volts, which remains below the 218 volt ANSI C84.1 Range A upper limit for a 208 volt system. If the panel recovers past roughly 206 volts overnight, a 6 percent correction will exceed that limit and a smaller boost is appropriate. This is why both the loaded and unloaded readings are needed before selecting a unit.

Can a buck-boost transformer correct voltage imbalance between phases?

No. A buck-boost transformer applies the same fixed ratio to each phase, so it raises or lowers all three together and preserves whatever imbalance already exists. If one line-to-line reading differs noticeably from the other two, the cause is usually unbalanced single-phase loading, a high-resistance connection or a utility-side problem, and it needs to be found and fixed. Phase imbalance overheats three-phase motors far faster than a uniformly low voltage does.

Should I correct one machine or the whole subpanel?

Correct the single machine when one piece of equipment is faulting and the rest of the panel is unaffected, since the amperage requirement and the installation are both smaller. Correct the subpanel when several loads show symptoms, when more equipment will be added, or when the sag affects everything behind that panel equally. Panel-level correction requires totaling the full-load amps of everything that runs at the same time, so it needs a higher amperage rating than a single-machine unit.