SJ Magnetics 1,500 kVA three-phase, liquid-filled pad-mounted transformer with 12470V delta primary and 480Y/277 secondary. Aluminum windings, loop-feed connections, DOE efficiency, and a seven-position primary J-tap selector.
Quotes include a link to approve and pay online — no phone call needed.
| Brand | SJ Magnetics |
| Rated Power | 1,500 kVA |
| Phase | Three Phase |
| Primary Voltage | 12470V delta |
| Secondary Voltage | 480Y/277 |
| Primary Configuration | Delta |
| Secondary Configuration | Wye with neutral |
| Vector Group | Dyn1 |
| Winding Material | Aluminum / Aluminum |
| Efficiency Standard | DOE |
| Cooling | ONAN |
| Insulating Fluid | Mineral oil |
| Temperature Rise | 65°C |
| Part # | SJ-PM-1500KVA-12470D-480Y-JT-AL |
| Feed Configuration | Loop feed |
| Primary BIL | 95 kV |
| Secondary BIL | 30 kV |
| Primary Connections | Six 15kV, 200A wells + inserts |
| Secondary Connections | Four spade terminals |
| Primary Taps | 4 above / 2 below nominal; 7 positions |
| Tap Schedule | 14400V (+15.48%); 13800V (+10.67%); 13200V (+5.85%); 12700V (+1.84%); 12470V (0.00%); 12000V (-3.77%); 11700V (-6.17%) |
| Loadbreak Switch | One 4-position LBOR |
| Fuse Protection | Bayonet + ELSP |
| Tank Finish | Munsell 7GY3.29/1.5 |
| Lead Time | 12-16 weeks |
The SJ Magnetics 1,500 kVA pad-mounted transformer supplies 480Y/277 power from a 12470V delta distribution system. Its delta-wye winding arrangement provides a neutral for the secondary system.
Aluminum primary and secondary windings operate in mineral oil with natural oil and air cooling. The seven-position J-tap selector allows the primary connection to be matched to the supply voltage while maintaining the selected secondary voltage.
The loop-feed design includes a four-position loadbreak switch and bayonet fuses backed by ELSP current-limiting fuses. Liquid level, temperature, and pressure/vacuum gauges support routine inspection, while the pressure relief, fill, and drain/sample valves provide service access.