In-stock units ship same business day (575) 228-1390  ·  [email protected]  ·  Request a Quote

6.64 kVA Step-Down Buck-Boost Transformer, 245V → 230V, 16.7A, Three Phase

by Sanzo Sales · Part # TX-BB-245D-230D-16.7A

$618.62

6.64 kVA three-phase buck-boost that bucks 245V to 230V (6% correction) at 16.7A. Encapsulated NEMA 3R, cETLus listed. In-stock ships same business day.

Full specifications ↓

✔ In Stock: 13

Specifications

BrandSanzo Sales
PhaseThree Phase (3-PH), Delta
Capacity6.64 kVA
Primary Voltage245V
Primary Amperage15.6A
Secondary Voltage230V
Secondary Amperage16.7A
Maximum Primary OCP20A
Frequency50/60 Hz
Insulation180°C
Temperature Rise115°C
Transformer TypeBuck/Boost
Part #TX-BB-245D-230D-16.7A
ConfigurationEncapsulated Autotransformer
Primary TerminationLead Wires & Terminal Lugs
Secondary TerminationLead Wires & Terminal Lugs
Termination Access(6) ¾" NPT Hubs
Winding MaterialAluminum
Enclosure MaterialSteel
Finish ColorANSI 70 Light Grey
Weatherproof RatingNEMA 3R
Certification ListingcETLus
Dimensions (W×H×D)9.25 × 7.25 × 5.75 in
Weight24 lb

Product Description

The TX-BB-245D-230D-16.7A is a 6.64 kVA three-phase buck-boost transformer that bucks a 245V supply to 230V — a 6% voltage correction — bringing 230V-rated equipment back into its proper operating range. Wired as an encapsulated buck transformer (autotransformer), it carries only the correction portion of the load, so this unit corrects a much larger connected load: up to 16.7A at 230V (6.64 kVA usable line capacity).

Resin-encapsulated in a NEMA 3R steel enclosure (ANSI 70 light grey) for indoor or outdoor mounting at the disconnect. Lead wires and terminal lugs, aluminum windings, 180°C insulation system, 115°C rise, 50/60 Hz, cETLus listed. Supplied as a two-unit open-delta bank for three-phase delta service. In-stock units ship the same business day.