4.35 kVA Step-Up Buck-Boost Transformer (Booster), 220V → 242V, 10.4A, Three Phase

by Sanzo Sales · Part # TX-BB-220D-242D-10.4A
4.9 out of 5 · 268 customer reviews(opens the reviews page)

$378.22

10.4A three-phase delta buck-boost transformer for 220V to 242V nominal step-up voltage correction, rated for up to 10.4 A continuous output. Match the supply voltage, equipment voltage and load current before ordering. This autotransformer corrects voltage without electrical isolation; output varies with incoming supply conditions and load.

Full specifications ↓

✔ In Stock: 24

Availability is rechecked when the order is accepted.

Specifications

BrandSanzo Sales
PhaseThree Phase (3-PH), Delta
Capacity4.35 kVA
Primary Voltage220V
Primary Amperage11.44 A
Secondary Voltage242V
Secondary Amperage10.4 A
Maximum Primary OCP15 A maximum input fuse or nonadjustable breaker
Frequency50/60 Hz
Insulation180°C
Temperature Rise115°C
Transformer TypeBuck/Boost
Part #TX-BB-220D-242D-10.4A
ConfigurationEncapsulated Autotransformer
Primary TerminationLead Wires & Terminal Lugs
Secondary TerminationLead Wires & Terminal Lugs
Termination Access1/2" NPT
Winding MaterialAluminum
Enclosure MaterialSteel
Finish ColorANSI 70 Light Grey
Weatherproof RatingNEMA 3R
Certification ListingcETLus
Dimensions (W×H×D)4.77 × 8.07 × 3.86 in
Weight24 lb

Product Description

The TX-BB-220D-242D-10.4A is a three-phase delta step-up buck-boost transformer for applications with a nominal 220V supply and equipment requiring 242V. It raises the supply voltage to help match the equipment's operating range. The finished-product rating is 10.4 A continuous output, with 4.35 kVA capacity at the calculated output voltage.

Select the right voltage and capacity

Compare the equipment nameplate voltage and running current with this product's ratings. Circuit-breaker size alone does not establish the connected load. For motors, compressors or multiple loads, check starting requirements, duty cycle and the total simultaneous current with the equipment manufacturer or qualified installer.

Will the output stay at exactly 242V?

The 242V designation is the nominal application voltage. Output is not regulated and changes with incoming voltage and load. Compare the expected operating range with the equipment's permitted voltage range rather than assuming a fixed output under every condition.

Match the electrical system

This product is intended for three-phase delta applications. The stated input and nominal output voltages are line-to-line values. It does not create a neutral. Buck-boost autotransformers provide voltage correction without electrical isolation. If electrical isolation is required, select an appropriate isolation transformer instead.

Plan the installation

Use the specification sheet, dimensional drawing and installation instructions matched to this exact part number. Review mounting clearances, conductor sizing, overcurrent protection and grounding before installation. Electrical work must be performed by qualified personnel with power disconnected.

See the specifications and product documents on this page for detailed ratings and installation requirements. Need help selecting a transformer? Use the transformer sizing calculator or request a quote with your supply voltage and equipment nameplate information.