In-stock units ship same business day (575) 228-1390  ·  [email protected]  ·  Request a Quote

15 kVA Step-Down Buck-Boost Transformer, 122V → 114V, 131.58A, Single Phase

by Sanzo Sales · Part # TX-BB-122V-114V-15KVA
4.9 out of 5 · 255 customer reviews(opens the reviews page)

$732.66

15 kVA single-phase buck-boost that bucks 122V to 114V (7% correction) at 131.58A. Encapsulated NEMA 3R, cETLus listed. In-stock ships same business day.

Full specifications ↓

✔ In Stock: 34

Specifications

BrandSanzo Sales
PhaseSingle Phase (1-PH), AC
Capacity15 kVA
Primary Voltage122V
Primary Amperage122.95A
Secondary Voltage114V
Secondary Amperage131.58A
Maximum Primary OCP175A
Frequency50/60 Hz
Insulation180°C
Temperature Rise115°C
Transformer TypeBuck/Boost
Part #TX-BB-122V-114V-15KVA
ConfigurationEncapsulated Autotransformer
Primary TerminationLead Wires & Terminal Lugs
Secondary TerminationLead Wires & Terminal Lugs
Termination Access(6) ¾" NPT Hubs
Winding MaterialAluminum
Enclosure MaterialSteel
Finish ColorANSI 70 Light Grey
Weatherproof RatingNEMA 3R
Certification ListingcETLus
Dimensions (W×H×D)5.43 × 10.87 × 4.49 in
Weight34 lb

Product Description

The TX-BB-122V-114V-15KVA is a 15 kVA single-phase buck-boost transformer that bucks a 122V supply to 114V — a 7% voltage correction — bringing 114V-rated equipment back into its proper operating range. Wired as an encapsulated buck transformer (autotransformer), it carries only the correction portion of the load, so this unit corrects a much larger connected load: up to 131.58A at 114V (15 kVA usable line capacity).

Resin-encapsulated in a NEMA 3R steel enclosure (ANSI 70 light grey) for indoor or outdoor mounting at the disconnect. Lead wires and terminal lugs, aluminum windings, 180°C insulation system, 115°C rise, 50/60 Hz, cETLus listed. Use two units in open-delta for three-phase delta systems, three for wye. In-stock units ship the same business day.