25 kVA Step-Down Buck-Boost Transformer, 240V → 200V, 72.17A, Three Phase

by Sanzo Sales · Part # TX-BB-240D-200D-25KVA
4.9 out of 5 · 255 customer reviews(opens the reviews page)

$3,878.07

25 kVA three-phase buck-boost that bucks 240V to 200V (17% correction) at 72.17A. Encapsulated NEMA 3R, cETLus listed. In-stock ships same business day.

Full specifications ↓

✔ In Stock: 1

Specifications

BrandSanzo Sales
PhaseThree Phase (3-PH), Delta
Capacity25 kVA
Primary Voltage240V
Primary Amperage60.14A
Secondary Voltage200V
Secondary Amperage72.17A
Maximum Primary OCP80A
Frequency50/60 Hz
Insulation180°C
Temperature Rise115°C
Transformer TypeBuck/Boost
Part #TX-BB-240D-200D-25KVA
ConfigurationEncapsulated Autotransformer
Primary TerminationLead Wires & Terminal Lugs
Secondary TerminationLead Wires & Terminal Lugs
Termination Access(6) ¾" NPT Hubs
Winding MaterialAluminum
Enclosure MaterialSteel
Finish ColorANSI 70 Light Grey
Weatherproof RatingNEMA 3R
Certification ListingcETLus
Dimensions (W×H×D)7.68 × 12.2 × 6.38 in
Weight120 lb

Product Description

The TX-BB-240D-200D-25KVA is a 25 kVA three-phase buck-boost transformer that bucks a 240V supply to 200V — a 17% voltage correction — bringing 200V-rated equipment back into its proper operating range. Wired as an encapsulated buck transformer (autotransformer), it carries only the correction portion of the load, so this unit corrects a much larger connected load: up to 72.17A at 200V (25 kVA usable line capacity).

Resin-encapsulated in a NEMA 3R steel enclosure (ANSI 70 light grey) for indoor or outdoor mounting at the disconnect. Lead wires and terminal lugs, aluminum windings, 180°C insulation system, 115°C rise, 50/60 Hz, cETLus listed. Supplied as a two-unit open-delta bank for three-phase delta service. In-stock units ship the same business day.